Panasonic KNX Power Supply 320/640 mA (PS132 / PS164)

DIN-rail KNX power supplies in 320 mA (PS132) and 640 mA (PS164) versions that supply and monitor the KNX bus line voltage. Each has one choked KNX bus output and one unchoked 30 V DC auxiliary output, both overload and short-circuit protected, and the units are VDE-certified.
2 models · datasheets · Authorised Panasonic KNX distributor in the UAE

Overview

What it does.

Every KNX line needs a power supply. The PS132 and PS164 are DIN-rail units that feed and monitor the bus voltage, rated at 320 mA and 640 mA, so you can size the supply to the number of devices on each line.

Each unit has a choked KNX bus output and an unchoked 30 V DC auxiliary output, both protected against overload and short circuit, and the range is VDE-certified. Skyline supplies them from Abu Dhabi for villas, towers and fit-outs across the UAE.

Typical applications

  • Villa and apartment distribution boards
  • Floor-level KNX lines in offices and hotels
  • Riser and plant-room panels
  • Adding lines to an expanding KNX installation

Key features

  • Two versions for bus loads of 320 mA and 640 mA
  • Integrated choke output for the KNX bus line plus an unchoked auxiliary output
  • Line over-voltage protection on the AC mains input
  • Overload and short-circuit protection on both outputs
  • Status LED for normal operation and overload
  • Compact DIN4 size (4 modules at 18 mm)
  • VDE-certified; meets EMC and LVD requirements

Technical data

Specifications.

Mains voltage230 V AC, 50/60 Hz
KNX bus output voltage28...31 V DC (SELV)
Auxiliary (30 V DC) output voltage28...31 V DC (SELV)
Rated current (bus + 30 V DC)320 mA (PS132), 640 mA (PS164)
Short-circuit current (bus + 30 V DC)700 mA (PS132), 1300 mA (PS164)
Overload LED thresholdOutput current above 500 mA (PS132) / 900 mA (PS164)
Mains failure bridging time> 100 ms
Power consumption (normal)13.9 W (PS132), 25.6 W (PS164)
Power consumption (max., overload)20.4 W at 500 mA (PS132), 35.3 W at 900 mA (PS164)
Leakage loss (open-circuited)0.85 W
Leakage loss (normal)3.5 W (PS132), 4.9 W (PS164)
Dimensions (H x W x D)90 x 71.8 x 65.8 mm
Mounting35 mm top-hat rail (TH35), 4 modules at 18 mm
Protection typeIP20
Overvoltage categoryIII
Pollution degree2
Operating temperature-5 ... +45 C
Storage temperature-10 ... +55 C
Ambient humidity5...93 % (non-condensing)
Weight217.3 g
CertificationVDE-certified (ISO/IEC 14543-3)

Ordering

Models & order codes.

Tap “Add to enquiry” to put a model code in the quote form below.

Model codeDescriptionEnquire
WRKT20305NCKNX Power Supply 320 mA (PS132)Add to enquiry
WRKT20315NCKNX Power Supply 640 mA (PS164)Add to enquiry

FAQ

Common questions.

Should I choose the PS132 or the PS164?

The PS132 is rated 320 mA and the PS164 640 mA for the bus plus the 30 V DC output. Add up the bus current of the devices on the line and pick the version with headroom. Skyline can check this against your device list.

Is there protection and status indication?

Yes. Both outputs are overload and short-circuit protected, the mains input has line over-voltage protection, and a status LED shows normal operation and overload.

How do I get a quote for the KNX power supply?

Send your quantities through the quote form or WhatsApp +971 50 759 8275 and Skyline will confirm availability and quote. We supply projects in all UAE emirates.

Enquire

Need KNX Power Supply (PS132 / PS164)?

Skyline is an authorised Panasonic KNX distributor in the UAE. Send the model codes and quantities and we'll reply with availability and a quote. We can also design, program and install the system.

More system devices

Request a quote

Tell us what you need. We reply with availability and a quote, usually the same working day.

We respect your privacy · UAE PDPL compliant